24V DC DIN-Rail Router Power Budget, Derating & Antenna Coax

Add the loads on a 24V DC DIN-rail router supply, calculate its derated output in a hot cabinet, and match external cellular antenna coax to the router.

By DIN Rail Router Guide Editorial 3 min read

Add the maximum input currents of the DIN-rail router and all devices sharing its 24 V DC supply. Keep that total below the supply’s derated output current at the hottest expected air temperature around it. For a metal cabinet, plan to place the cellular antenna outside. Omron sizing guide, RECOM derating guide, Teltonika antenna guide.

Start with the shared 24 V load

Check that each device accepts 24 V DC. Make one row for each load that can run at the same time and use its applicable maximum input current. If a device specifies maximum input power at 24 V, divide those watts by 24 V to get amps. Omron sizing guide.

Example loadPublished supply dataCurrent to budget
Phoenix Contact TC ROUTER 4102T-4G EU WLAN10 to 30 V DC input. Typical draw at 24 V is below 180 mA.1.50 A, published maximum. Router technical data
Phoenix Contact FL SWITCH 241619.2 to 32 V DC input. The manufacturer lists maximum draw at minimum input voltage and maximum ambient temperature.0.39 A, using that published maximum as the budget allowance. Switch technical data
Total allocated current1.50 A + 0.39 A1.89 A

Derate the supply for cabinet temperature

Look up the output rating and temperature derating for the exact supply. Use the hottest expected ambient temperature at its mounting location. Check the specified mounting direction, spacing and any derating for input voltage or altitude. Omron installation guidance, RECOM derating guide, STEP3 technical data.

The Phoenix Contact STEP3-PS/1AC/24DC/2.5/PT is rated at 24 V DC and 2.5 A. Its output derates by 2% of rated output per degree above 50 °C through 70 °C. The calculation below assumes the rated 24 V output setting, 120 V AC input, horizontal DIN-rail mounting with specified clearance and an altitude of 2,000 m or less. STEP3 technical data.

Air temperature at supplyAvailable output current at 24 VCurrent left after the 1.89 A allocation
50 °C2.50 A0.61 A
60 °C2.50 A × (1 − 10 × 0.02) = 2.00 A0.11 A
65 °C2.50 A × (1 − 15 × 0.02) = 1.75 A−0.14 A

At 60 °C the example fits the steady-load budget with 0.11 A left. At 65 °C, choose a supply with more available output at that temperature or move enough load to a separate supply. Check the router’s own operating temperature separately. Phoenix Contact lists −40 °C to 70 °C for this router. Omron sizing guide, Router technical data.

Check startup and voltage at the loads

Compare the published startup current of the loads that start together with the supply’s startup and overload specifications. Loads within the steady rating can still delay or prevent the output from rising at startup. Omron sizing guide.

For long DC runs, account for the worst-case cable voltage drop at each load. Compare the resulting terminal voltage with the input range in the load table. The switch in this example needs at least 19.2 V at its input. RECOM voltage-drop guidance, Switch technical data.

Route the antenna coax outside the cabinet

  1. Match the external cellular antenna to the LTE bands the router uses and the connectors on its cellular ports. For a MIMO setup, connect one antenna element to each designated MIMO port. Teltonika antenna guide.
  2. Connect the cellular coax to the cellular sockets. Identify them by the radio and connector type listed below for the example router. Router technical data.
  3. Mount the antenna outside the metal cabinet and keep the coax run short. If the antenna must sit farther away, use low-loss coax. Use an outdoor-rated antenna for exposed locations. Teltonika mounting guidance.
RadioSockets on the example routerMatching lead
CellularTwo 50 Ω SMA female socketsSMA male cellular coax
Wi-FiTwo RSMA female socketsA matching reverse-polarity SMA Wi-Fi lead

Router connector specifications, Teltonika connector guidance.

Evidence and limits. The calculation is based on Phoenix Contact’s online technical data for parts 1234353, 1043416 and 1088491. Guidance was drawn from Omron, RECOM’s October 2024 guide and Teltonika Networks. The pages were checked on November 26, 2026. No hardware tests were performed.

Sources

  1. Omron industrial power supply selection guide
  2. RECOM DIN-rail power supply selection guide
  3. Phoenix Contact TC ROUTER 4102T-4G EU WLAN technical data
  4. Phoenix Contact FL SWITCH 2416 technical data
  5. Phoenix Contact STEP3-PS/1AC/24DC/2.5/PT technical data
  6. Teltonika Networks router antenna selection and mounting guide